Hi all,
Thank you for reading. I have a bunch of solar power equipment that I purchased, but my solar guy bailed on me so I am DIYing. I have installed small systems in the past, but generally I would call myself a beginner/intermediate in terms of knowledge.
I have 4/0 cable running from my array to the house. How do I connect this cable to my MNPV6-250? I believe the largest bus bar connection is 1/0. I am not finding specs for the output lug on the the DIN rail, but it looks about 1/0 as well. I will need electrical cable reducers on both ends of my cable run, for both the combiner box connections and the inverter connections. Ideas?
thank you
It sure is big and bulky and cumbersome, but it was already in place and buried in the ground from a former low voltage (12 volt) system with a long run...
So I elected to use it to save time and money, both of which are in short supply I have two Solar World 285 Watt, 31 Volt panels and a Outback flexmax60 MPTT controller. The cable is aluminum so I guess that added to the size.
No worries Is the cable in conduit & pictures always help explain..
So for Voltage drop they used hard strand commercial cable , I understand .
So tell us your everything of distance & everything , spend time to explain everything , we have Very smart folks here & they will always help ! They helped me , So Seee !!
I need help
VT & good folks here , just explain ALL makes it so much easier than pulling teeth
Quote from: ClassicCrazy on June 04, , 10:48:16 PM
How about something like this for 4/0 to smaller cable ? Use antioxidant on the aluminum cable connection and torque well and recheck later. This one says only 2/0 but maybe a larger one is available.
http://www.galco.com/buy/Marathon-Special-Products/?source=googleshopping&gclid=Cj0KEQjw-Mm6BRDTpaLgj6K04KsBEiQA5f20E6oQ3vJYgSkzC2jT6kyvwRwztNTus9IBI8V_jWyJersaAqRY8P8HAQ
Larry
I have used those and they come in literally huge sizes. Very easy to mount and use.
Tom
Thanks for the suggestions! What about something like this?
It's a compression fitting - tin plated copper. Goes from 4/0 to #2, but it says for stranded wire. My wire is solid. I wonder if that would make a difference? Can I mix AL with CU?
The cable is not in conduit - direct burial.
I'm working on the design for putting my system together. The best resources I have found for how to wire it up are the user manuals for the combiner box and the charge controller. I tried to find some solar power books to help, but they all get very abstract when it comes to wiring... When I have my design done, I will post and ask for a review.
Quote from: pablo on June 05, , 12:46:47 PM
Thanks for the suggestions! What about something like this?
It's a compression fitting - tin plated copper. Goes from 4/0 to #2, but it says for stranded wire. My wire is solid. I wonder if that would make a difference? Can I mix AL with CU?
The cable is not in conduit - direct burial.
Hi pablo,
OK, #4/0 AWG cable IS HUGE. Running this huge cable that is SOLID in conduit is extremely difficult, and therefore quite uncommon, in my experience.
Are you absolutely certain that this cable is 4/0 and solid ?? Not to insult you, but this seems beyond an extreme combination.
The Box Lugs in those terminal blocks are almost always used with stranded cable. Often the range of conductor size is limited for the use of solid conductors.
FWIW, Vic
Thanks for checking Vic! Gosh, I feel like an idiot now. I just went out and double checked and it is 1/0. My AWOL solar guy had wanted me to use 4/0 for battery to inverter connection and I must have switched oughts in my poor dilapidated brain.
So that should make things easier. Thanks again for taking the risk of insulting me.
I cut off a chunk of the 1/0 (by the way a ratcheted pipe cutter works great for this) and tested it in my combiner box. It fits into the bus bars and the rail lug, but not into the breaker switch.
Why not just shave down the diameter of the aluminum at the end of the cable to make it fit? wouldn't that be better for electrical flow than using an adaptor and smaller wire?
Quote from: pablo on June 05, , 03:38:58 PM
Why not just shave down the diameter of the aluminum at the end of the cable to make it fit? wouldn't that be better for electrical flow than using an adaptor and smaller wire?
Not sure of the long term effects of just lopping off some of the diameter but it should not affect resistance / voltage drop.
wire resistance is rated by diameter and length so a stubby reduction will not be an issue and it seems certainly less than a lug, terminal block, etc.
Be careful not to nick solid wire it can break at a nick easily.
If I did this I would use a dremel tool or somesuch to carefully shave off diameter all around with a rounded shoulder between full size and reduced end (Not square)
Just from here.
Tom